Advantages of IT Panels (Isolated Power Panels):
Active Isolated Power Systems prevent the people in the environment from being harmed in case of any failure.
It prevents power cuts that may occur due to insulation failure.
The fault current in the electrical system is constantly monitored and reduced to non-critical levels.
It ensures the continuity of power supply for all medical areas, including the operating room, cardiac areas and intensive care units, which is the most critical of energy continuity.
Electrical fault monitoring is guaranteed.
With it panels, the risk of fire caused by leakage currents is eliminated.
Protection of high-cost medical devices against electrical failures is provided.
Additional leakage currents are collected and prevented from reaching critical values.
It is ensured that the operations continue without interruption.
Areas where IT Panels (Isolated Power Panels) are used in hospitals:
Operating theaters
Operating room preparation room, plaster room and recovery rooms
Intensive care units
Anesthesia rooms
Cardiac catheterization chambers
Angiographic examination rooms
Premature baby rooms
IT BOARDS (Medical Isolated Power Panels)
These panels are used in the power supply of places in medical locations within the scope of Group 2. Panels are comply with TS IEC 60364-7-710 standarts. Typical medical isolated power panels are consist of an isolating transformer, insulation monitoring device detect insulation resistance, load current, transformer temperature, system, earth, CT connections, alarm indicator, equipotential bonding terminal. Electrical loads in Group 2 locations are protected against short circuit currents with fuses appropriate to IT sistem.
Technical Specifications |
Brand |
ELEKTROVIEN |
Type |
MIPP / 1P-XX |
Standarts |
TSE-IEC 60364-7-710 |
Output Power |
3,15 / 4 / 5 / 6,3 / 8 / 10 kVA |
Supply Input |
Single phase Mono phase Line |
Rated Line Voltage |
230 VAC |
Frequency |
50 / 60 Hz |
Isolation Level |
3 kV / 1 min. |
Input Protection |
gL Fuse |
Output Voltage |
230 VAC |
Output Protection |
2 Pole Fuse |
Watchdog |
IsolaIstion Resistance by LCD Screen |
Alarm output |
Insulation Fault, Overload, Over temperature |
Functional Test |
AdvancedInsulation Fault |
Enclosure Leakage Current |
<0,5 mA |
Isolation fault detection period |
<1 s |
Working Temperature |
0°C / 50°C |
Storage Temperature |
-15°C / 70°C |
Panel Dimensions |
1700 x 500 x 500 mm |
Ventilation |
with Fan |
Protection Class |
IP 41 |
Colour |
RAL 9003 or RAL7035 |
Distibution Output |
6 - 12 - 18 - 24... Pcs |
IT PANELS WITH TRANSFER UNIT
Medical isolated power panels with transfer unit; are used in the system is fed from two different power supply to provide power continuity of isolated power systems. In addition to isolated power panels, these panels have transfer unit provide switching between two paralel power source. Transfer unit follow two supply line and when voltage values exceed limit values, provide transfering between lines as automatically. In these way, interruption of energy is prevented and critical loads is always fed.
Technical Specifications |
Brand |
ELEKTROVIEN |
Type |
MITPP / 1P-XX |
Standarts |
TSE-IEC 60364-7-710 |
Output Power |
3,15 / 4 / 5 / 6,3 / 8 / 10 kVA |
Supply Input |
Double Single Phase Line |
Rated Line Voltage |
230 VAC |
Frequency |
50 / 60 Hz |
Isolation Level |
3 kV / 1 min. |
Input Protection |
gL Fuse |
Output Voltage |
230 VAC |
Output Protection |
2 Pole Fuse |
Watchdog |
IsolaIstion Resistance by LCD Screen |
Alarm output |
Insulation Fault, Overload, Over temperature |
Functional Test |
Advanced Insulation Fault and Transfer Test |
Enclosure Leakage Current |
<0,5 mA |
Isolation fault detection period |
<1 s |
Working Temperature |
0°C / 50°C |
Ventilation |
with Fan |
Protection Class |
IP 41 |
Colour |
RAL 9003 or RAL7035 |
Transfer Time |
< 5 ms. |
Response Range |
50 - 500 k Ω |
Distibution Output |
6 - 12 -18 - 24... Pcs |
Panel Dimensions |
1700 x 500 x 500 mm |
IT PANELS WITH TRANSFER UNIT AND FAULT DETECTION SYSTEM
Medical isolated power panels with transfer unit and insulation fault detection device have also test signal generator, insulation fault evaluators and toroidal transformer in apart from other isolated panels. When any fault exist, this fault is detected by insulation monitoring device and test signal generator produce a test signal, after that fault detected according to response of system to this signal. Insulation fault evaluator send signal to alarm monitoring devices.
Technical Specifications |
Brand |
ELEKTROVIEN |
Type |
MITFPP / 1P-XX |
Standarts |
TSE-IEC 60364-7-710 |
Output Power |
3,15 / 4 / 5 / 6,3 / 8 / 10 kVA |
Supply Input |
Double Single Phase Line |
Rated Line Voltage |
230 VAC |
Frequency |
50 / 60 Hz |
Isolation Level |
3 kV / 1 min. |
Input Protection |
gL Fuse |
Output Voltage |
230 VAC |
Output Protection |
2 Pole Fuse |
Watchdog |
Isolation Resistance by LCD Screen |
Alarm output |
Insulation Fault, Overload, Over temperature |
Functional Test |
Advanced Insulation Fault and Transfer Test |
Enclosure Leakage Current |
<0,5 mA |
Isolation fault detection period |
<1 s |
Working Temperature |
0°C / 50°C |
Storage Temperature |
-15°C / 70°C |
Panel Dimensions |
1700 x 500 x 500 mm |
Ventilation |
with Fan |
Protection Class |
IP 41 |
Colour |
RAL 9003 or RAL7035 |
Transfer Time |
< 5 ms. |
Response Range |
50 - 500 k Ω |
Distibution Output |
6 - 12 - 18 - 24... Pcs |